Circuitbreakers


Electrical theory Acronyms Installation standards Capacitors SupplySystems Automation Sensors Controllers and modules Control and Safety MicroProcessor PCboard References About us

Electrical theory
Acronyms
Installation standards
Capacitors
SupplySystems
Automation
Sensors
Controllers and modules
Control and Safety
MicroProcessor
PCboard
References
About us

 

Circuit breakers

Definition:

Circuit breaker:- A manually (or remote) operated device capable of making, carrying and breaking its rated current under specified normal circuit conditions and also automatically breaks (opens) a circuit under specified over current conditions such as overload and short circuit currents.  

 

Circuit breaker technolgies:
  1. Thermal and or magnetic:
  2. Hydraulic magnetic:
  3. Electronic,

Acronyms:

***See page acronyms for a comprehensive list

SCPD Short-Circuit Protective Device
   
MCB Miniature circuit breaker - 0.5 o 125Amp,
MCCB A circuit breaker having a supporting housing of moulded insulating material forming an
integral part of the circuit breaker (IEC 947-2).
ACB Air circuit breaker
In  Nominal trip current indicated on CB.

 

Zero current circuit breakers: See acronyms and definitions
Energy limiting circuit breakers: See acronyms and definitions

Concept of a current limiting circuit breaker:

Interrupting short-circuit current:-
As an example, let us consider a quick acting, current limiting circuit breaker a described previously.
To limit the short-circuit current already at its initiation, the main contacts must be opened by the striker within a few milliseconds.

A very fast acting device may need less than 1ms for this. An arc is struck immediately, which driven towards the arc chamber, delivers a high arc voltage.

As a simplification, the arc voltage can be considered as an equivalent additional resistance connected in series to the current circuit which immediately limits the rising short-circuit current.

 

 

What is this "let through energy" definition in terms of math:

1 joule per second equals 1 watt

The short circuit current curve look like a short parabola and that is defined as x2 so:  

E= ∫i2 dt - meaning it is the area below the curve.

According to the calculus rule it is calculated as I2t joules.  

or also:

Power = VI = I2R in watts

and so

Electrical energy= Power(watts) x time = (I2 x R) x time (seconds) in Joules.

but what if the R is so small compared to I one can ignore it, then Energy = I2t joules  

***Maybe the mathematicians out there will kill me for this but it is how I understand it.

 

---------------=============-------------

--------------===========---------------

 
ABB    
------

 

------

   

 

---------=============----------

 

 
In depth look at the tripping curve:

 selective short-circuit (S),

---------===========---------

 

 

-----------==========--------

 
 

Tripping curves:

         
B        
C        
D        
E        
F        
         
1        
2        
2,3(LL)        
4        

-----------------

 

Analysis of a short circuit:-

Terms to DIN EN 60 909-0 VDE 0102/0103 for short-circuit currents in three-phase systems

Peak short-circuit current (ip): The maximum permissible instantaneous value of the anticipated short
circuit current.

Note: The value of the peak short-circuit current depends on the moment when the short-circuit

occurs. Calculation of the peak short-circuit current in a three-pole short-circuit refers to the

conductor and the moment at which the maximum possible current occurs.
 

Sustained short-circuit current Ik: The effective value of the short-circuit current which is retained once all
transient reactions have decayed.

Initial symmetrical short-circuit current Ik˝
The effective value of the symmetrical AC component of an anticipated short-circuit current at the moment of occurrence of the short-circuit, if the short-circuit impedance retains the value at the time zero.
 

Illustration: Progression of the short-circuit current over time with remote short-circuit (diagrammatic representation).
Ik˝ Initial symmetrical short-circuit current
ip Peak short-circuit current
ik Sustained short-circuit current
iDC Decaying DC component of the short-circuit current
A Initial value of DC component iDC
Thermal short-circuit current I

 

-------=======----------

The short-circuit current reaches its peak value after a quarter of the sinusoidal period, which is 5 milliseconds for 50Hz supply (4.2ms in the case of 60Hz as in the USA), assuming that the current is symmetrical, i.e. initiated at a current zero. This is to be prevented.

 

 

Summary: circuit breaker as load break switch

 

Below is the different processes: How shall a circuit breaker be rated(selected):

How is it selected for overload current protection
SANS10142: 6.7.x IEC 60364

 

NEC Article 230.42

SANS give pre-requisites for components first.

For a circuit breaker it must, at a specific voltage (considering the circuit power factor) and the fault current equalling its rated breaking capacity or lower be capable of breaking the circuit. gs

5.1.3 - EFP

5.2.5 - protection equipment

7.13 hiV apparatus

2.2.1 South African standards

SANS 152 (SABS 152), Low-voltage air-break switches, air-break disconnectors, air-break switch-disconnectors

SANS 156 (SABS 156), Moulded-case circuit-breakers.

SANS 556-1, Low-voltage switchgear – Part 1: Circuit-breakers.

SANS 767-1 (SABS 767-1), Earth leakage protection units – Part 1: Fixed earth leakage protection circuit-breakers.

SANS 61008-1/IEC 61008-1, Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs) – Part 1: General rules.

SANS 3.71 short-circuit protective device SCPD device intended to protect a circuit or p

A

 

  An interesting note I found in NEC article 100 definitions:  was that the automatic means does not have to be an integral part of the circuit breaker - that is a surprise. gs

UL 508, Industrial control equipment.

 

6.7 Protection
6.7.1 Overcurrent protection
NOTE The term over current protection includes both overload protection (see 6.7.2) and short-circuit protection (see 6.7.3).

6.7.1.1
Each protective device shall have a rated current that does not exceed the lowest of the current-carrying capacities of any of the conductors of the circuit and shall have a minimum short-circuit rating of 2,5 kA.
 

6.7.2 Overload protection

6.7.2.1 Overload protection:
The rated current of the overload protective device shall not
exceed the current-carrying capacity of the conductor it protects, except in the case of circuits in which the presence of overload protection could create a dangerous situation, such as in circuits for lifting magnets

BTW: No mention of the component current ratings?gs

Table 6.26
Maximum
circuit breaker rating(A)
 
Cable size mm2
10 1
16 1,5
25 2,5

PS: Don't make the mistake of thinking this is all to it, depending on what the circuit is used for the dictation changes. gs



 

4.4.4.1

Reference:- ABB Comparison of tripping characteristics for miniature circuit-breakers

For protection against overload, the protective device must be selected  based on the current carrying capacity

Ib In  Iz (standard)

Idesign Icb  Icable (gs)

and

I2 1.45 x Iz (standard)

Ioperation 1.45 x Icable (mine)

Ib= Design current of a circuit

In= Rated current of the protective device

Iz= Current carrying capacity of the cable in accordance with IEC/HD 60364-5-52

I2 = Current ensuring effective operation in the conventional time of the protective device

IEC 60364-4-43h

 


Where a feeder supplies continuous loads or any combination of continuous and non-continuous loads, the rating of the over current device shall not be less than the non-continuous load plus 125% of the continuous load.

Exception: Where the assembly including the overcurrent devices protecting the feeder(s) are
listed for operation at 100% of their rating, neither the ampere rating of the overcurrent device nor the ampacity of the feeder conductors shall be less than the sum of the continuous load plus the noncontinuous load.

Only breakers listed for 100% application,
and so labelled can be applied under the exception (for example loads Frame and R Frame 140G’s that are specifically marked and rated 100%).

Breakers without a 100% application listing and label are applied at 80% of rating
 

I could not find above in NEC 2011 - so I struck it through. 

This is in 2011:

II. Branch-Circuit Ratings 210.19 Conductors — Minimum Ampacity and Size.
(A) Branch Circuits Not More Than 600 Volts.
(1) General. Branch-circuit conductors shall have an ampacity not less than the maximum load to be served.

Where a branch circuit supplies continuous loads or any combination of continuous and noncontinuous loads, the minimum branch-circuit conductor size, before the application of any adjustment or correction factors, shall have an allowable ampacity not less than the noncontinuous load plus 125 percent of the continuous load.


Exception: If the assembly, including the overcurrent devices protecting the branch circuit(s), is listed for operation at 100 percent of its rating, the allowable ampacity of the branch circuit conductors shall be permitted to be not less than the sum of the continuous load plus the noncontinuous load.
 

Informational Note No. 1: See 310.15 for ampacity ratings of conductors.
Informational Note No. 2: See Part II of Article 430 for minimum rating of motor branch-circuit conductors.
Informational Note No. 3: See 310.15(A)(3) for temperature limitation of conductors.

 

Meaning:

For <=600V circuits

Icable>=Iload

For assembly NOT listed for 100% operation:

***Not considering adjustment factors.

Mixed loads(Non-Cont and Cont) Icable>Sum of Inoncont +125%Icont

For assembly listed for 100% operation:

Mixed loads(Non-Cont and Cont) Icable > Sum of Inoncont + Icont

=============

(B) Overcurrent Devices Rated 800 Amperes or Less.
The next higher standard overcurrent device rating (above the ampacity of the conductors being protected) shall be permitted to be used, provided all of the following conditions are met:
 

(1) The conductors being protected are not part of a branch circuit supplying more than one receptacle for cord
and-plug-connected portable loads.
 

(2) The ampacity of the conductors does not correspond with the standard ampere rating of a fuse or a circuit
breaker without overload trip adjustments above its rating (but that shall be permitted to have other trip or
rating adjustments).
 

(3) The next higher standard rating selected does not exceed 800 amperes.
(C) Overcurrent Devices Rated over 800 Amperes.

 Where the overcurrent device is rated over 800 amperes, the ampacity of the conductors it protects shall be equal to or greater than the rating of the overcurrent device defined in
240.6.

Meaning: Except if a small conductor (the lord alone knows what this is) If <800amp one an select a one size higher fuse - as long as such size is <800Amp.

For higher the 800Amp it must be same as cable or by some 240.6

 

 

b) Opening under overload conditions

1) Instantaneous or definite time-delay operation

The release shall cause tripping of the circuit-breaker with an accuracy of i10 O/. of the tripping current value of the current setting for all values of current setting of the overload release.

2) Inverse time-delay operation. Conventional values for inverse time-delay operation are given in table 6.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60 947-2

Opening under overload conditions

7.2.1 .2.4 : b

1) Instantaneous or definite time-delay operation

The release shall cause tripping of the circuit-breaker with an accuracy of i10 O/. of the tripping current value of the current setting for all values of current setting of the overload release.

meaning: CB accuracy < +-10% of for all values of Ir (gs)

2) Inverse time-delay operation Conventional values for inverse time-delay operation are given in table 6.

Table 6 simply says

for lower/equal to 63Amps - at 1.05In circuit must trip after 1 hr only, if then raised to 1.3In it must trip ONLY within 1hr

At bigger then 63amps it becomes 2hr

They talk about this time as conventional time.

At the reference temperature (see 4.7.3) and at 1,05 times the current setting (see 2.4.37 of Part 1), i.e. with the conventional non-tripping current (see 2.5.30 of Part 1), the opening release being energized on all phase poles, tripping shall not occur in less than the conventional time (see 2.5.30 of Part 1) from the cold state, i.e. with the circuit-breaker at the reference temperature.

Meaning: 1.05Ir @Tref no tripping within 1hr (gs) at cold state

Moreover, when at the end of the conventional time the value of current is immediately raised to 1,30 times the current setting, i.e. with the conventional tripping current (see 2.5.31 of Part 1), tripping shall then occur in less than the conventional time later.

Meaning: At 1.3Ir tripping must occur in less than conventional time(gs) (conventiaonal time is that In<63A->1hr and In>63Amp->2 hr)

------------

NOTE The reference temperature is the ambient air temperature on which the time-current characteristic of the circuit-breaker is based. 4.7.3

4:7:3: Unless otherwise specified
– Non thermal overloads no change -5 “C to +40 ‘C;

-Thermal overloads - reference temperature of +30 “C +- 2 “C. Manufacturer shall provide variations data (see 7.2.1.2.4, item b)).

2:4:37: - and 2:5:30 could not find references

 

 
 

DEFINING THE TRIPPING CURVE

4.7.4 Tripping time setting of over-current releases


1) Definite time-delay over-current releases
The time-delay of such releases is independent of the over-current.

 The tripping time setting shall be stated as the duration in seconds of the opening time of the circuit-breaker, if the time-delay is not adjustable, or the extreme values of the opening time~ if the time delay is adjustable.


2) Inverse time-delay over-current releases
The time-delay of such releases is dependent on the over-current.

The time/current characteristics shall be given in the form of curves supplied by the manufacturer.

These shall indicate how the opening time, starting from the cold state, varies with current within the range of operation of the release.

The manufacturer shall indicate, by suitable means, the tolerances applicable to these curves.
These curves shall be given for each extreme value of the current setting and, if the time setting for a given current setting is adjustable, it is recommended that they be given in addition for each extreme value of the time setting.
 

NOTE It is recommended that the current be plotted as abscissa and the time as ordinate, using logarithmic scales.

Furthermore, in order to facilitate the study of co-ordination of different types of over-current protection,

!t is recommended that the current be plotted as multiples of the setting current and the time in seconds on the standard graph sheets detailed in 5.6.1 of IEC 60269-1 and in figures 4(l), 3(11) and 4(11) of IEC 60269-2-1.

 
     

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-------------------

-------------============------------

Circuit breaker Reference temperature:

   lS/lEC 60947-2:2003  
 

Unless otherwise specified – the operating value of overload releases other than those of the thermal type is independent of the ambient air temperature within the limits of -5 “C to +40 ‘C;

for releases of the thermal type, the values stated are for a reference temperature of +30 “C, +- 2 “C. The manufacturer shall be prepared to state the influence of variations in the ambient air temperature (see 7.2.1.2.4, item b)).

Meaning:

4:7:3: Unless otherwise specified
– Non thermal overloads no change -5 “C to +40 ‘C;

-Thermal overloads - reference temperature of +30 “C +- 2 “C. Manufacturer shall provide variations data (see 7.2.1.2.4, item b)).

 

 

--------------=============------------

 

And the impedance?

BS EN 60947-2 - calculating Zs    
In this case Zs is determined from the basic equation:- Zs Ia≤ UoCmin– which transposes to: - Zs≤ ((UoCmin)/Ia) where:-
 

Uo is the nominal voltage to earth.
Ia is the current required to achieve the disconnection time as given in the Regulations.
 

Cmin is the minimum voltage factor to take account of voltage variations depending on time and place, changing of transformer taps and other considerations.
 

NOTE: For a low voltage supply given in accordance with the Electricity Safety, Quality and Continuity. Regulations 2002 as amended, Cmin is given the value 0.95.

 

 

   
Art: 110

And short circuit currents:

SANS10142: 6.7.3 IEC NEC 2011 Art 110
6.6.1.15 Switchgear shall be fully rated for withstanding the prospective short-circuit current that could occur at that point in the system, unless series-connected (cascaded) systems are applied in accordance with
6.7.4.

6.6.1.16 Where the prospective fault level of the supply cannot be determined, a fault current meter may be used (see 8.5.2).
 

6.6.1.17 All disconnecting devices in a distribution board
a) shall be protected by a fully rated short-circuit protective device, and
b) when used in combination with a short-circuit protective device (see 6.7.4), shall have a conditional short-circuit current rating (see 3.22.1) appropriate to its condition of installation, but of not less than 2,5 kA

 

 Short-circuit protection
6.7.3.1 At its point of installation, a short-circuit protective device shall be capable of breaking any over current up to the value of the prospective short-circuit current. (See also 6.7.4 on cascaded systems.)

----------IEC 60 364----------

4.4.5.5.1 The rated breaking capacity shall be not less than the prospective maximum short-circuit current at the place of its installation, except cascading.

CB kA> circuit shortcircuit at point(gs)

4.4.5.5.2 For cables and insulated conductors, all current caused by a short-circuit occurring at any point of the circuit shall be interrupted in a time not exceeding that which brings the insulation of the conductors to the permitted limit temperature.
Meaning: Tshort max < Cable temp rise to limit time (at that current(gs)

For operating times of protective devices <0.1 s where asymmetry of the current is of importance and for current-limiting devices

k2xS2 shall be greater than the value of the let-through energy (I2t) quoted by the manufacturer of the protective device.

Meaning: if Tshort<0.1 Table 43A applies (special I think) (gs)- We depend on let through energy of CB

For short-circuits of duration up to 5 s, the time t, in which a given short-circuit current will raise the insulation of the conductors from the highest permissible temperature in normal duty to the limit temperature can, as an approximation, be calculated from the formula:

 

t = (k * s/l)Squared

t = time it will take to reach this max (sec)
S is the cross-sectional area, in mm2;
I is the effective short-circuit current, in A, expressed as an r.m.s. value;
k is a factor taking account of the resistivity, temperature coefficient and heat capacity of the conductor material, and the appropriate initial and final temperatures. For common conductor
insulation, the values of k for line conductors are shown in Table 43A.

Meaning: Ensure t is quick enough (ONLY applicable if Tshort <=5sec) 

---Additionally: IEC 60947-2: for CB---

 

7.2.5 Ability to make and break under short-circuit conditions

Subclause 7.2.5 of Part 1 applies with the following amplifications:

The rated short-circuit making capacity shall be in accordance with 4.3.5.1(Rated short circuit making capacity) and 4.3.5.3 (Standard relationship between short-circuit making and breaking capacities and related power factor, for a.c. circuit-breakers)

The rated short-circuit breaking capacity shall be in accordance with 4.3.5.2

The rated short-time withstand current shall be in accordance with 4.3.5.4

NOTE It is the manufacturer’s responsibility to ensure that the tripping characteristic of the circuit-breaker IS compatible with the capability of the circuit-breaker to withstand the inherent thermal and electrodynamlc stresses

---============-----

and the association shall comply with the requirements of 7.2.1.2.4, item a)

-----===========----

7.2.1 .2.4 Opening by over-current releases a)

Opening under short-circuit conditions

The short-circuit release shall cause tripping of the circuit-breaker with an accuracy of 20% of the tripping current value of the current setting for all values of the current setting of the short-circuit current release.

Where necessary for over-current co-ordination (see 2.17), the manufacturer shall provide Information (usually curves) showing. maximum cut-off (let-through) peak current (see 2.5 19 of Part 1) as a function of prospective current (r, m.s. symmetrical);

— /2t characteristics (see 2.18) for circuit-breakers of utilization category A and, if applicable,

 B for circuit-breakers with instantaneous override (see note to 8.3.5).

Conformity with this information may be checked during the relevant type tests in test sequences II and Ill (see 8.3.4 and 8.3.5).

NOTE It may be possible to provide other forms of data to verify co-ordination characteristics of circuitbreakers, for example, tests on combinations of short-circuit protective devices.

Rated short-time withstand current (Icw)

The rated short-time withstand current of a circuit-breaker is the value of short-time withstand current assigned to that circuit-breaker by the manufacturer under the test conditions specified In 8.3.6.2.

 For a.c., the value of this current is the r.m.s value of the a,c. component of the prospective short-circuit current, assumed constant during the short-time delay.

The short-time delay associated with the rated short-time withstand current shall be at least 0,05 s,

 

Preferred values being as follows:

0,05 –0,1 –0,25–0,5–1 S

The rated short-time withstand current shall be not less than the appropriate values shown in table 3

Table 3- Minimum values of rated short-time withstand current

In = CB rated current

In <2500 ->12xIn or 5 kA, whichever is the greater

In >2500 ->30 kA

 -------------============--------

 

 

 

110.9 Interrupting Rating.Equipment intended to interrupt current at fault levels shall have an interrupting ratin
not less than the nominal circuit voltage and the current thais available at the line terminals of the equipment.
Equipment intended to interrupt current at other than fault levels shall have an interrupting rating at nominal circuit voltage not less than the current that must be interrupted.
 

110.10 Circuit Impedance, Short-Circuit Current Ratings, and Other Characteristics.

The overcurrent protective devices, the total impedance, the equipment shortcircuit current ratings, and other characteristics of thecircuit to be protected shall be selected and coordinated to permit the circuit protective devices used to clear a fault to do so without extensive damage to the electrical equipment
of the circuit.

This fault shall be assumed to be either between two or more of the circuit conductors or between an
circuit conductor and the equipment grounding conductor(s) permitted in 250.118.

Listed equipment applied in
accordance with their listing shall be considered to meet the requirements of this section.

======

230.208 Protection Requirements. A short-circuit protective device shall be provided on the load side of, or as an integral part of, the service disconnect, and shall protect all
ungrounded conductors that it supplies.

 

The protective device shall be capable of detecting and interrupting all values of current, in excess of its trip setting or melting point, that can
occur at its location.

A fuse rated in continuous amperes not to exceed three times the ampacity of the conductor,

or a circuit breaker with a trip setting of not more than six times the ampacity of the conductors, shall be considered as providing the required short-circuit protection.

 

Found his table from Panel design Rittal - to be completed

------------=============-----------

 

Circuit breaker Utilisation categories

  IEC 60947.2: 4.4:  
  Table 4- Utilization categories
Category A

Circuit-breakers not specifically intended for selectivity under short-circuit conditions with respect to other short-circuit protective devices in series on the load side, i.e. without an intentional short-time delay provided for selectivity under short-circuit conditions, and therefore without a short-time withstand current rating according to 4.3.5.4.

Category B

Circuit-breakers specifically intended for selectivity under short-circuit conditions with respect to other short-circuit protective devices in series on the load side, i.e. with an intentional short-time delay (which may be B adjustable), provided for selectivity under short-circuit conditions. Such circuit-breakers have a short-time withstand current rating according to 4.3.5.4.

NOTE Selectivity is not necessarily ensured up to the ultimate shortcircuit breaking capacity of the circuit-breakers (for example in the case of operation of an instantaneous release) but at least up to the value  specified in table 3.

table 11 (see 8.3.2.2.4 and 8,3.2,2.5),

NOTE 2 Attention is drawn to the different requirements for the minimum required percentage of lc~ for utilization categories A and B, in accordance with table 1.

NOTE 3 A circuit-breaker of utilization category A may have an intentional short-time delay provided for selectivity under conditions other than those of short circuit, with a short-time withstand current less than that according to table 3. In that case, the tests include test sequence IV (see 8.3.6) at the assigned short-time

 
  4.3.5.4:

 

 
  Table 11

 

 
  Hager: •Ref:Electricians handbook courtesy of Larson and Toubro - India: 

*I dont have 60 898

IEC classifies MCBs into three category depending upon their “Quality of current
limiting” & let through energy of a circuit breaker on short circuits. Permissible let to energy values for circuit breakers with rated current up to and including 16A as per

EN60898 are:
Class 1 No limitation
Class 2 290 kA²S
Class 3 84 kA²S -

*All Hager mcb are class 3

 

 
------------=============------------

Where must it be installed? 

 

south Africa

SANS10142: 6.7.1.1

Europe +

IEC 60364

 

USA+

UL489

UL1077

 

Canada


CSA c22.2 No 5.02CSA c22.2 No 235-04

 

  china

GB 14048-2

6.7.2.2 Overload must be installed at point of conductor reduction OR - with a switch/disconnector OR earth-leakage unit that requires overload protection.

UNLESS

The over current device can sit anywhere in the cable as long as no connections to/from it

AND

entire length protected against shorts circuit OR

cable shorter then 5mtrs

not near flammable materials

not likely to cause humans harm

I spent a lot of time trying to get to grips with this - I get this feeling this commission could not get consensus the matter of "anywhere in the cable"...thus the strange additions. Flammable and human safety? Really?

Now the challenge: Overload unit can be anywhere in the cable but the whole cable must be short circuit protected?

Mechanical protection or another electrical component?

Are we confusing motor overload protection with cable / reticulation protection here?

G-2 CASES WHERE SHORT-CIRCUIT PROTECTION DOES NOT NEED TO BE PLACED AT THE ORIGIN OF BRANCH CIRCUIT

With reference to 4.4.5.2.1and Fig. G.1, short-circuit protective device P 2may be moved up to 3 m from the origin (O) of the branch circuit (S2) provided that there is no other connection or socket-outlet on this length of the branch circuit, and in the case of 4.4.5.2.1
the risk of short-circuit, fire and danger to persons is reduced to a minimum for this length.

but:

4.4.4.2 Position of devices for overload protection
4.4.4.2.1 A device ensuring protection against overload shall be placed at the point where a change, such as a change in cross-sectional area, nature, method of installation or in constitution,
causes a reduction in the value of current-carrying capacity of the conductors, except where
4.4.3.2.2and 4.4.3.3 apply.

4.4.4.2.2 The device protecting the conductor against overload may be placed along the run of that conductor if the part of the run between the point where a change occurs (in cross-sectional area, nature, method of installation or constitution) and the position of the protective device has neither branch circuits nor socket-outlet circuits and fulfils at least one of the following two conditions:
a) it is protected against short-circuit current in accordance with the requirements stated in 4.4.5;
b) its length does not exceed 3 m, it is carried out in such a manner as to reduce the risk of shortcircuit to a minimum, and it is installed in such a manner as to reduce to a minimum the risk of
fire or danger to persons (see also 4.4.5.2.1).
NOTE: For installation according to a) see Figure F.1.
For installation according to b) see Figure F.2

 

.

       
           
6.7.2.3The overload protective device may be installed at any point in the conductor run that it protects, provided that

a) there is no branch circuit or socket-outlet between the point where there is a reduction in the conductor's current-carrying capacity and the point where the device is installed, and


b) the entire length of the conductor is protected against short-circuit, or
 

c) the conductor is
1) of length not exceeding 5 m,
2) so installed as to minimize the risk of overload or fault in its operating condition,
3) not near flammable materials, and
4) not likely to cause harm to a person in the event of a fault

         
Now short circuit protection is as plain and simple as "installed at the point of reduction" - as it should be!

6.7.3.2

 

AND SHORT CIRCUITS?

4.4.5.2 Position of devices for short-circuit protection A device ensuring protection against short-circuit shall be placed at the point where a reduction in the cross-sectional area of the conductors or another change causes a change to the current-carrying capacity of the conductors, except where 4.4.5.2.1, 4.4.5.2.2or 4.4.5.3 applies.
4.4.5.2.1 The various cases stated in the following sub clause shall not be applied to installations situated in locations presenting a fire risk or risk of explosion and where special rules for certain
locations specify different conditions. The device for protection against short-circuit may be placed other than as specified in 4.4.4.2, under the following conditions.

In the part of the conductor between the point of reduction of cross-sectional area or other change and the position of the protective device there shall be no branch circuits nor socket-outlet circuits
and that part of the conductor shall:
a) not exceed 3 m in length, and
b) be installed in such a manner as to reduce the risk of a short-circuit to a minimum,

and so forth and so forth...

 

       

...

Disconnection times - protection devices and RCD Gary

The higher the value of Uc, the higher the rapidity of supply disconnection required to provide protection (see Fig. F7). The highest value of Uc that can be tolerated indefinitely without danger to human beings is 50 V AC.

In DC the highest value of Uc that can be tolerated indefinitely without danger is 120 V.

Disconnecting-time limits (IEC 60364-4-41)

Mine: 4.2.11.3.2.2

Fig. F7 – Maximum disconnecting times (in seconds) for final circuits not exceeding 63 A with one or more socket-outlets, and 32 A supplying only fixed connected current-using equipment
Uo (V AC) 50 < Uo ≤ 120 120 < Uo ≤ 230 230 < Uo ≤ 400 Uo > 400
System TN 0.8 0.4 0.2 0.1
TT 0.3 0.2 0.07 0.04

Nota:

bulletin TN systems, a disconnection time not exceeding 5 s is permitted for distribution circuits, and for circuits not covered by Fig. F7
bulletin TT systems, a disconnection time not exceeding 1 s is permitted for distribution circuits and for circuits not covered by Fig. F7

For human protection an RCCB must have sensitivity of 30mA max and must trip within 40ms max at residual current of 150mA tba gs

Nb: Must add the details of the standards specifications on the actual tripping set point of an earth leakage device.gs

*Ref: Hager QZD009 Protection devices cat. pg. D26

 

IEC 60364  
4.4.4.3 Omission of devices for protection against overload
The various cases stated in this sub-clause shall not be applied to installations situated in locations presenting a fire risk or risk of explosion or where the requirements for special installations and locations specify different conditions.

4.4.4.3.1 General Devices for protection against overload need not be provided:
a) for a conductor situated on the load side of a change in cross-sectional area, nature, method of installation or in constitution, that is effectively protected against overload by a protective device placed on the supply side;


b) for a conductor that is not likely to carry overload current, provided that this conductor is  protected against short-circuit in accordance with the requirements of 4.4.4 and that it has neither branch circuits nor socket-outlets;


c) at the origin of an installation where the distributor provides an overload device and agrees that it affords protection to the part of the installation between the origin an d the main distribution point of the installation where further overload protection is provided.


d) for circuits for telecommunications, control, signalling and the like.
NOTE: For installations according to a), b) and d), see Fig. F.3.

 
   
   

 

 

Relevant standards and circuit breakers:

PS: This is a reference based on manufacturer material referring to the different standards - Excuse if you are specialist and find some discrepancy...just let us know - for this is always a work in progress we would be a happy to oblige.

Standards references to circuit breakers:

  UL ANSI NEC CSA

 

SANS IEC
Genl

Alsocheck: The requirements for overcurrent protection devices are for use in industrial cabinets
(Industrial Control Panels) anchored in the UL 508A

Mechanical engineering the NFPA 79 (Electrical
Standard for Industrial Machinery) and Safe on the North American market -

 

  Articles:

210 - Branch circuits

215 - Feeders

240 - Overcurrent Protection

430 - Motors, Motor Circuits, and Controllers
 controllers, and m

 

 

VC8035 -

VC8036 -

 

IEC 60947-2 (circuit breaker design and manufacturing)

IEC 60364, § 434.5.1 (electrical distribution network).

bulletIEC 947-4 - Circuit breakers with motor protective characteristics
 
MCB

UL1066 - LV AC and DC CB in Enclosures

 

- ANSI C37.13: IEEE Standard for Low-Voltage AC Power Circuit Breakers Used in Enclosures

- ANSI C37.16: Low-Voltage Power Circuit Breakers and AC Power Circuit Protectors.

Preferred Ratings, Related Requirements, and Application Recommendations

- ANSI C37.17: American National Standard for Trip Devices for AC and General

Purpose DC Low Voltage Power Circuit Breakers

     
bullet.60 898

 

 

MCCB UL 489 - NEC -Branch circuit protection. MCCB.

UL 489: Molded-Case Circuit Breakers, Molded-Case Switches and Circuit Breaker Enclosures

UL 489 MCCB: MCS(Molded Case Switches) & Circuit Breaker Enclosures.

bulletUL 489A - Branch circuit protection DC circuit breaker short circuit protection in communications equipment.
bulletUL1077 - Used in conjunction with CB for supplementary external device protection.
bulletBranch circuit protection.
bulletUL1077 - Used in conjunction with CB for supplementary external device protection.
bullet 
bulletUL486- evaluation of lugs connection in field wiring this includes items under UL489. 
bullet 

 

 

    CSA C22.2 No. 5. 5-02 - CEC - Canadian -

 

CSA C22.2 No.235 - Used in conjunction with CB for supplementary external device protection.

   
ACB            
Motor protection           IEC 947-4 - Circuit breakers with motor protective characteristics.
 
 

Coordination/Cascading/Backup protection notes

And lets dig deeper according to what standards say:

IEC 60 364

IEC 60947-2.2003

This gives procedure for the testing not method to confirm. Maybe this is outdated.

 

SANS
4.4.5.5.1 The rated breaking capacity shall be not less than the prospective maximum short-circuit current at the place of its installation, except where the following paragraph applies.

A lower rated breaking capacity is permitted if another protective device having the necessary breaking capacity is installed on the supply side.

In that case,

 the characteristics of the devices shall be coordinated so that the energy let through by these two devices does not exceed that which can be withstood without damage by the device on the load side and the conductors protected by these devices.

THIS IS ALL TO DO: Check that the source I2t energy is below a certain value for bottom component.

NOTE In certain cases other characteristics may need to be taken into account such as dynamic stresses and arcing energy for the device on the load side. Details of the characteristics needing coordination should be obtained from the manufacturers of the devices concerned.

So what does this mean - things are much, much easier now:

Not just for cascading but for anything below a circuit breaker...like a contactor or switch.

Knowing the let through energy of a supply SCPD one just has to ensure the load side component kA (over time) is higher than this. Its like choosing a fuse. 

Actually cascading table per supplier is redundant!

After this Confirm cable temp rise time to be within limits. There done.

60 947-2: ANNEX A

The term “coordination” includes consideration of discrimination (see 2,5.23 of Part 1 and
also 2,17,2 and 2.17.3) as well as consideration of back-up protection (see 2.5.24 of Part 1).
Consideration of discrimination can in general be carried out by desk study (see clause A.5),
whereas the verification of back-up protection (Cascading gs) normally requires the use of tests (see clause A,6).

Found no ref to 2.5.23

2.17.2:

Total discrimination (total selectivity) over-current discrimination where, in the presence of two over-current protective devices in series, the protective device on the load side effects the protection without causing the other protective device to operate

2.17.3
partial discrimination (partial selectivity)
over-current discrimination where, in the presence of two over-current protective devices in series, the protective device on the load side effects the protection up toa given level of over current, without causing the other protective device to operate

---------===========-------

The obvious is that the information all provided by manufacturer and the components comply to relevant standards.

Ultimately: The maximum conditional short-circuit current (see 2.5.29 of Part 1) shall not exceed the rated ultimate short-circuit breaking capacity of the SC PD.

C1=source cb

C2=load cb

IEC 60947.2.2003

A.5 Verification of discrimination
Discrimination can normally be considered by desk study alone, i.e. by a comparison of the
operating characteristics of C1 and the associated SCPD, for example, when the associated
SCPD is a circuit-breaker (C2) provided with an intentional time-delay,


The manufacturers of both the C1 and the SCPD shall provide adequate data concerning the relevant operating characteristics so as to permit Is to be determined for each individual association.

In certain cases, tests at Is are necessary on the association, for example
— when C1 is of the current-limiting type and C2 is not provided with an intentional time-delay;
— when the opening time of the SCPD is less than that corresponding to one half-cycle,
To obtain the desired discrimination when the associated SCPD is a circuit-breaker, an
intentional short-time delay may be necessary for C2.


Discrimination may be partial (see figure A.4) or total up to the rated short-circuit breaking
capacity Icu (or Ics) of C1. For total discrimination, the non-tripping characteristic of C2 or the pre-arcing characteristic of the fuse shall lie above the tripping (break-time) characteristic
of C1.
Two illustrations of total discrimination are given in figures A.2 and A.3.

Meaning: All they say is that the two cb curves must be adjacent in all respects at all times...other wise its only partially protected.

I.O.W C2 must be more sensitive / closer to the tripping points

A.6 Verification of back-up protection


A.6.1 Determination of the take-over current: -Compliance with the requirements of A.3,2 can be checked by comparing the operating characteristics of Cl and the associated SCPD for all settings of Cl and, if applicable, for all
settings of C2.

A.6.2 Verification of back-up protection
a) Verification by tests.
Compliance with the requirements of A.3.3 is normally verified by tests in accordance with A.6.3. In this case, all the conditions for the tests shall be as specified in 8.3.2.6 with the
adjustable resistors and inductors for the short-circuit tests on the supply side of the
association.

---------

A.3.3 Behaviour of Cl in association with another SCPD
For all values of over-current up to and including the short-circuit breaking capacity of the
association, Cl shall comply with the requirements of 7,2.5 of Part 1, and the association shall comply with the requirements of 7.2.1,2.4, item a).

7.2.5 Ability to make and break under short-circuit conditions

7.2.1 Operating conditions

Meaning: C1 must just be capable of switching SCC

 

---------
b) Verification by comparison of characteristics
In some practical cases and where the SCPD is a circuit-breaker (see figures A,4 and A.5),
it may be possible to compare the operating characteristics of Cl and of the associated
SCPD, special attention being paid to the following:
– the Joule integral value of C1 at its Icu and that of the SCPD at the prospective current of association;
– the effects on C1 (e.g. by arc energy, by maximum peak current, cut-off current) at the peak operating current of the SCPD.

Meaning: we need to know the I2t energy as % of RSCC

In some practical cases and where the SCPD is a circuit-breaker (see figures A,4 and A.5),
it may be possible to compare the operating characteristics of Cl and of the associated
SCPD, special attention being paid to the following:
the Joule integral value of Cl at its /CU and that of the SCPD at the prospective current of association;
– the effects on Cl (e.g. by arc energy, by maximum peak current, cut-off current) at the peak operating current of the SCPD.


The suitability of the association may be evaluated by considering the maximum total
operating I2t characteristic of the SCPD, over the range from the rated short-circuit breaking
capacity Icu(or Ics) of C1 up to the prospective short-circuit current of the application, but not
exceeding the maximum let-through I2t of C1 at its rated short-circuit breaking capacity or
other lower limiting value stated by the manufacturer.
NOTE Where the associated SCPD is a fuse, the validity of the desk study is limited up to Icu of

Confirm I2t of the cb mechanism of its capability to pass the I2t energy (Icu cb = Icu of SCPD but almost always they are the same so device...so?

A.6.3 Tests for verification of back-up protection
If C1 is fitted with adjustable over-current opening releases, the operating characteristics shall
be those corresponding to the minimum time and current settings,
If C1 can be fitted with instantaneous over-current opening releases, the operating
characteristics to be used shall be those corresponding to Cl fitted with such releases,
If the associated SCPD is a circuit-breaker (C2) fitted with adjustable over-current opening
releases, the operating characteristics to be used shall be those corresponding to the
maximum time and current settings.
If the associated SCPD consists of a set of fuses, each test shall be made using a new set of
fuses, even if some of the fuses used during a previous test have not blown

Where applicable, the connecting cables shall be included as specified in 8.3.2.6.4 except that,
if the associated SCPD is a circuit-breaker (C2), the full length of cable (75 cm) associated with
this circuit-breaker may be on the supply side (see figure A.6).
Each test shall consist of a O–t–CO sequence of operations made in accordance with 8.3.5 of
this standard, ‘whether at /Cu or /C~, the CO operation being made on Cl.
 

A test is made with the maximum prospective current for the proposed application, This shall
not exceed the rated conditional short-circuit (see 4.3.6.4 of Part 1),
 

A further test shall be made at a value of prospective current equal to the rated short-circuit
breaking capacity /Cu (or /CS) of Cl, for which test a new sample Cl may be used, and also, if
the associated SCPD is a circuit-breaker, a new sample C2.

a) if the associated SCPD is a circuit-breaker (C2):
– either both Cl and C2 shall trip at both test currents, no further tests then being
required.
 

This is the general case and provides back-up protection only.
– or C1 shall trip and C2 shall be in the closed position at the end of each operation, at
both test currents, no further tests then being required,
This requires that the contacts of C2 separate momentarily during each operation. In this
case restoration of the supply is provided, in addition to back-up protection (see note 1 to
figure A.4), The duration of interruption of supply, if any, shall be recorded during these
tests.
– or C1 shall trip at the lower test current, and both C1 and C2 shall trip at the higher test
current.
This requires that the contacts of C2 separate momentarily at the lower test current.
Additional tests shall be made at intermediate currents to determine the lowest current at
which both C1 and C2 trip, up to which current restoration of supply is provided. The
duration of interruption of supply, if any, shall be recorded during these tests.

– or C1 shall trip at the lower test current, and both C1 and C2 shall trip at the higher test
current.
This requires that the contacts of C2 separate momentarily at the lower test current.
Additional tests shall be made at intermediate currents to determine the lowest current at
which both C1 and C2 trip, up to which current restoration of supply is provided. The
duration of interruption of supply, if any, shall be recorded during these tests.
b) if the associated SCPD is a fuse (or a set of fuses):

In the case of a single-phase circuit at least one fuse shall blow;
— in the case of a multi-phase circuit either two or more fuses shall blow, or one fuse shall
blow and C1 shall trip.

A.6.4 Results to be obtained
Subclause 8.3.4.1.7 of Part 1 applies.
Following the tests, C1 shall comply with 8.3,5.3 and 8.3.5.4
In addition, if the associated SPCD is a circuit-breaker (C2), it shall be verified, by manual
operation or other appropriate means, that the contacts of C2 have not welded.

Above is the real tests conditions  to confirm cascading

 

 

 
 

 

 

...

 

AC circuit breakers and power factor:

Standard relationship between short-circuit breaking and making capacities and related power factor.

 

Table 2 -ratio n between short-circuit making capacity and short-circuit
breaking capacity and related power factor (for a.c. circuit-breakers)

Short-circuit breaking capacity I kA r.m.s. Power factor I Minimum value required for n

n=(short - circuit making capacity/short - circuit breaking capacity)

4,5 <= / <= 6
6 <= / <=10
10 <= / <= 20
20 <= I <= 50
50 <= /
0,7
0,5
0,3
0,25
0,2
1,5
1,7
2,0
2,1
2,2
     
     
     

NOTE: For values of breaking capacity lower than 4,5 kA, for certain applications, see table 11 for the power factor.

The rated short-circuit making and breaking capacities are only valid when the circuit-breaker
is operated in accordance with the requirements of 7.2.1,1 and 7.2. i.2.

For special requirements, the manufacturer may assign a value of rated short-circuit making
capacity higher than that required by table 2. Tests to verify these rated values shall be the
subject of agreement between manufacturer and user.

 

Manufacturers notes and ranges

MCCB range

ABB

Tmax - 15 to 3000Amps,

       
         
         
         

 

ACB (low voltage Power circuit breakers)

ABB:

Emax: 400 to 5000A

but I saw the SACE can go to 6300A

Models:

MF Fixed magnetic
MA Adj. magnetic

TMG Thermomagnetic release for generator protection
TMD Thermomagnetic release with adjustable thermal and fixed magnetic thresh
TMA Thermomagnetic release with adjustable thermal and magnetic threshold

       
         
         
         

 

Motor protection circuit breaker:-

This is special circuit breaker with a thermal trip characteristics that qualifies for overload protection of a motor.

So what's special about that, a normal circuit breaker will do?

The tripping  curve of a normal circuit breaker does not bring together the magnetic tripping curve the more accurate thermal tripping curve as a motor - overload protector.

Essentially the normal circuit breaker would serve as a short circuit protector and separate motor overload would be used.

The motor protection circuit breaker combines the two components.

See blog: Can a normal circuit breaker be used as a motor protection.       

Two considerations apply:

For short circuit protection of a circuit (which is what the traditional CB provide the standards say:

Fig. 1.4-3: Tripping curve of a circuit breaker with motor protective characteristics.

The grey line indicates the current from of a normal motor. After the rated speed is reached (here after about 1.5s), the starting current (6 x In) reduces to the rated current of the motor(1xIn).
a) Time-current characteristic of the bimetallic release
b) Time-current characteristic of the magnetic release
c) Characteristic of the motor

 

 

Drawing notations:

 

To do:

Whenever possible, the SCPD shall be located on the supply side of Cl.

If the SCPD is located on the load side, it is essential that the connection between Cl and the SCPD be so arranged
as to minimize any risk of short circuit.
NOTE In the case of interchangeable releases, these considerations should apply to each relevant release.

Really? Should this even be an option?

A.3.2 Take-over current
For the purpose of back-up protection the take-over current Ib shall not exceed the rated
ultimate short-circuit breaking capacity Icu of C1 alone (see figure A.4)

 

A.3.3 Behaviour of Cl in association with another SCPD
For all values of over-current up to and including the short-circuit breaking capacity of the
association, C1 shall comply with the requirements of 7,2.5 of Part 1

-------=============-

 

-------=========-------

http://download.schneider-electric.com/files?p_File_Id=666795087&p_File_Name=0860CT0201R1114-net.pdf

SO – then what is UL489 and UL1077 – Where does it fit in with the rest?

UL 489 Circuit Breakers

Used for branch circuit protection, internal/external receptacles, external motors and HACR equipment

(heating, air conditioning and refrigeration).

UL 1077 Supplementary Protectors

Used for overcurrent protection within appliances or electrical equipment, where branch circuit protection

is already provided or not required.

Note:UL 489 devices can be used in place of UL 1077; UL 1077 devices cannot be used in place of UL 489.

Doc: UL489 & UL1077 CB Eaton PG01101007E

 

Bad Mitsubishi website: http://www.mitsubishielectric.com/fa/products/lv_distri/lvc-breakers/mccb/index.html#pageUnit01


 

Downloads page: http://www.mitsubishielectric.co.jp/haisei/lvs_ws/downloads/catalogs.htm#wss

-----------=========-------

Mitsubishi

Double-Break System

Until now, ultra breakers have been used when an

even higher short-circuit breaking capacity is required in

a large-capacity power distribution system for a big

building project. The ultra breaker is configured with a

normal main circuit breaker and an additional cur-rent-limiting unit connected in series to the main

breaker. The current-limiting unit is equipped with sin-gle-pole double-break type repulsive parallel conduc-tors. This unit, together with the main breaker, provides

a single-pole triple-break series interruption to generate

a high arc voltage, resulting in superior current-limiting

performance to suppress the short-circuit current.

For the WS-V Series, we have developed a new

ultra breaker, which employs an internal double-break

 

“Guide to low voltage circuit breakers standards.pdf” – When a fault current between Ics and Icu occurs twice or more – the continued operation of the CB must be verified

 

(Ics: short-circuit breaking capacity guaranteed for three consecutive breaking

operations). Really?

The blowout coils are placed alternately because the magnetic flux from each coil also exerts a…”MitsubishiElectric-MCCB info 133_complete.pdf”

------------============--------------

Best company for MCCB specifications? Mitsubishi although there website for reference material downloads…leaves much to be desired. If Google does not show the back doors you will not get any download ref. material.

Best company to share the “essence of considerations for designing a product line. See doc “Essence of newline circuitbreaker “133”.pdf

Also Mitsubishi in my search to declare in introduction MCB good for DC and up/down connections – I am not sure is this just an oversight from other mnf. BH-D10 is actually a DC CB? Does this mean the others do not comply?

Although it is in the same doc when one notes Mits. MCB is not noted as IEC 60 947-2 compliant but only EN 60 898 – Maybe doc is old 2011?

 

My CB selection for motor protection has always been simple.

What is the Main supply CB value in ka- the coordination applies – CB Ampacity rated according to the cable size to will supply the motor. That’s it. But it seems out there is all kinds of considerations even factor of x2 or 3 motor size? Really?

Hager even have some intellectual chart considering the starting curve of motor application – I always thought the starting curve could be a dynamic entity and over time for any application will deteriorate including variances in temperature for one.

See ProtectionDevicesMCB.pdf

Or what if one could just size the MCCB according to motor size…You are looking for trouble. Lets see how you battle to start a high inertia loaded star/delta

-----------=========--------

Did you know?

In any case there is only a select few special ciruitbreakers designed to operate at continuously 100% rated load?

Does not make sense does it? Most manufacturers recommend Iload=80%FRC (Full rated current)

But no one says it – do they?

Well for one – the thermal effect on Therm/magnetic circuit breakers alone accounts for having to over rate the CB

Eaton/mccb/tbo120003e.pdf

 

 

SAFETY AND PROTECTION DEVICES

OSHA 1910.334 -  from http://www.ieee.org/index.html    

Use of Equipment (b) Electric power and lighting circuits.

(2) Reclosing circuits after protective device operation. After a circuit is de-energized by a circuit protective device, the circuit protective device, the circuit may not be manually

reenergized until it has been determined that the equipment and circuit can be safely energized. The

repetitive manual reclosing of circuit breakers or  reenergizing circuits through replaced fuses is prohibited.

Note: When it can be determined from the design of the circuit and the overcurrent devices involved that the automatic operation of a device was caused by an overload rather than a fault condition, no examination of the circuit or connected equipment is needed before the circuit is reenergized.

64

 

   

SEE HERE FOR THE COMPLETE POST / TOPIC LIST.

 

References: Thank you to the following who unwittingly or wittingly collaborated to build knowledge. For any infringements, apologies. Let us know here:

Copyright issues